No.
Items
Reverse Power 2
38.
Set
Loss
Excitation
39.
Fault 1
Loss
Excitation
40.
Fault 2
Power Factor Low
41.
1
Power Factor Low
42.
2
Switch Setting
1.
Close Time
2.
Open Time
3.
Check Time
Analog Sensor Setting
Temperature Sensor
1.
Curve Type
2.
Open Circuit
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Parameters
Defaults
(0-1)
1
(0-200.0)%
5.0
(0-200.0)%
3.0
(0-3600)s
5
(0-7)
1
(0-1)
1
(0-200.0)%
20.0
(0-200.0)%
18.0
(0-3600)s
5
(0-7)
1
(0-1)
1
(0-200.0)%
20.0
(0-200.0)%
18.0
(0-3600)s
5
(0-7)
0
(0-1)
1
(0-1.00)
0.70
(0-1.00)
0.75
(0-3600)s
5
(0-7)
1
(0-1)
0
(0-1.00)
0.70
(0-1.00)
0.75
(0-3600)s
5
(0-7)
0
(0-20.0)s
5.0
(0-20.0)s
3.0
(0-20.0)s
5.0
(0-15)
8
(0-7)
1
Description
Action
0: Disable
1: Enable
Set value is percentage of rated active
power.
Return value is percentage of rated active
power.
Delay value
Action
0: Disable
1: Enable
Set value is percentage of rated reactive
power.
Return value is percentage of rated reactive
power.
Delay value
Action
0: Disable
1: Enable
Set value is percentage of rated reactive
power.
Return value is percentage of rated reactive
power.
Delay value
Action
0: Disable
1: Enable
Set value is gen power factor.
Set value is gen power factor.
Delay value
Action
0: Disable
1: Enable
Set value is gen power factor.
Set value is gen power factor.
Delay value
Action
Pulse width of switch on. When it is 0, it
means output constantly.
Pulse width of switch off. When it is 0, it
means output constantly.
Feedback and check time of breaker close
status input.
SGD
0: None; 1: Warning; 2: Block; 3: Safety Trip;
Page 66 of 116