Smartgen HGM9510N User Manual page 33

Paralleled genset controller
Table of Contents

Advertisement

No
Type
37
PLC Function Alarm
38
DIN16 Comm. Failure
39
DIN16 Input Alarm
DOUT16
40
Failure
41
AIN24 Comm. Failure
AIN24 Cylinder Temp.
42
High
AIN24 Exhaust Temp.
43
High
AIN24 Cylinder Temp.
44
Difference High
45
AIN24 Sensor Open
46
AIN24 Sensor High
47
AIN24 Sensor Low
48
Power Factor Low
49
THD High
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
When PLC function is set users-defined and if it is active, the controller
will initiate an alarm signal.
It is detected in the detection range set by the PLC function.
When DIN16 communication is enabled and the controller cannot
receive the communication data, it will initiate an alarm signal l.
It is always detected.
When DIN16 input is set users-defined and if it is active, the controller
will initiate an alarm signal.
It is detected in the detection range set in the input.
When DOUT16 communication is enabled and the controller cannot
Comm.
receive the communication data, it will initiate an alarm signal.
It is always detected.
When AIN24 communication is enabled and the controller cannot
receive the communication data, it will initiate an alarm signal.
It is always detected.
When this is enabled and the controller detects cylinder temperature
has exceeded the pre-set value, it will initiate an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold".
When this is enabled and the controller detects exhaust temperature
has exceeded the pre-set value, it will initiate an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold".
When this is enabled and the controller detects cylinder temp.
difference has exceeded the pre-set value, it will initiate an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold".
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
When over high alarm is enabled, and the controller detects the sensor
value is above the preset upper limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold" when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
When over low alarm is enabled, and the controller detects the sensor
value is below the preset lower limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold" when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
When this is enabled and the controller detects that the generator
power factor has fallen below the pre-set limit, it will initiate an alarm
signal.
It is always detected.
When this is enabled and the controller detects that the THD has
exceeded the pre-set limit, it will initiate an alarm signal.
Description
Page 33 of 116

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm9530n

Table of Contents