Smartgen HGM9510N User Manual page 51

Paralleled genset controller
Table of Contents

Advertisement

No
Type
28
Oil Pressure Low
Oil Pressure Sensor
29
Wrong
30
Fuel Level Sensor Open
31
Fuel Level Low
32
Flex. Sensor 1 Open
33
Flex. Sensor 1 High
34
Flex. Sensor 1 Low
35
Flex. Sensor 1 Wrong
36
Flex. Sensor 2 Open
37
Flex. Sensor 2 High
38
Flex. Sensor 2 Low
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
When this is enabled, and the controller detects the pressure is below
the preset limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold".
When voltage or current input is selected for the curve type of the
controller, and the controller detects input signal is abnormal, it shall
issue an alarm signal, and meanwhile the curve is transferred to
resistor type to prevent damaging the controller.
It is always detected.
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
When this is enabled, and the controller detects the level is below the
preset limit, it shall issue an alarm signal.
It is always detected.
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
When over high alarm is enabled, and the controller detects the sensor
value is above the preset upper limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold" when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
When over low alarm is enabled, and the controller detects the sensor
value is below the preset low limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold" when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
When voltage or current input is selected for the curve type of the
controller, and the controller detects input signal is abnormal, it shall
issue an alarm signal, and meanwhile the curve is transferred to
resistor type to prevent damaging the controller.
It is always detected.
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
When over high alarm is enabled, and the controller detects the sensor
value is above the preset upper limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold" when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
When over low alarm is enabled, and the controller detects the sensor
value is below the preset low limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold" when the
Description
Page 51 of 116