ProSoft Technology ProTalk PTQ-PDPMV1 User Manual page 165

Profibus dp master network interface module for quantum
Table of Contents

Advertisement

PTQ-PDPMV1 ♦ Quantum Platform
PROFIBUS DP Master Network Interface Module for Quantum
6.2.5 Mailbox Message: Get Live List
This command returns 127 bytes of information about the nodes on the network.
Every byte stands for one bus subscriber, and the position of the byte in the
response data assigns the address (0 to 126). The content assigns the Station
Type.
This command can be sent in all operation modes (that is, STOP, CLEAR, and
OPERATE); however, the module must be initialized properly.
Parameter
Command Initiator
Command Name
Command Number
Fragmented
Extended Header Data
Command and Response Layout: Get Live List
Message ID
Message information
Command
Data size
Frame count
Frame number
Offset high
Offset low
Extended word 1
Extended word 2
Extended word 3
Extended word 4
Extended word 5
Extended word 6
Extended word 7
Extended word 8
Message Data byte 1
Message Data byte 2
Message Data byte 3
Message Data byte "n"
Message Information
Refer to Message Information (page 180).
ProSoft Technology, Inc.
August 12, 2014
Description
Application
GET LIVE LIST
1800h
No
Fault information may be returned in the header of the response.
Command
(ID)
0240h
1800h
0000h
0100h
0100h
0000h
0000h
-
-
-
-
-
-
-
-
...
Response
(ID)
0200h
1800h
Get Live List
7F00h
127 Bytes of Data
0100h
0100h
0000h
0000h
-
-
-
-
-
-
Return Code
Fault Information
Station Type 0
Response Data Byte 1
Station Type 1
Response Data Byte 1
Station Type 2
Response Data Byte 1
...
Response Data Byte 1
Station Type 126
Response Data Byte 1
Mailbox Messaging
User Manual
Page 165 of 306

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ProTalk PTQ-PDPMV1 and is the answer not in the manual?

Questions and answers

Table of Contents