Power quality
3. Configure the settings as needed:
IEC 61000-4-30 Setup
4. Click Send to save your changes.
The Advanced PQ screen shows the new configuration.

Configuring EN 50160

To configure EN 50160:
1. Select EN50160 Enable.
If you want to delete all logged EN 50160 data, click Reset, and then click Yes to confirm.
2. Click Edit to configure your meter's EN 50160 logging parameters.
3. Configure the settings as needed:
EN 50160 Setup
201
Parameter
Description
Select if you want to enable IEC 61000-4-30 monitoring.
Enabled
NOTE: This option must be enabled when monitoring EN 50160 or
IEEE 519 parameters.
Specifies the percentage of nominal voltage that defines a disturbance.
Threshold
For example, if you set this to 10% of 120 V nominal, the disturbance
occurs when the voltage dips to 12 V and below.
Specifies the percentage above the Threshold that defines the end of
the disturbance. For example, if you set this to 2%, the end of the
Hysteresis
disturbance occurs when the voltage rises to (10% + 2%) of nominal, or
14.4 V and above.
Log 4-30 3s
Select if you want to enable IEC 61000-4-30 3-second interval data
measurements
logging.
Log 4-30 10s
Select if you want to enable IEC 61000-4-30 10-second interval data
measurements
logging.
NOTE: You must enable IEC 61000-4-30 before the meter can start monitoring EN 50160
parameters.
Parameter
Description
Enabled
Select if you want to enable EN 50160 monitoring.
Nominal Voltage Specifies the nominal voltage value used for EN 50160.
Nominal
Specifies the nominal frequency used for EN 50160.
Frequency