Configuration and Value View via Web Pages
3.2.2
Configuration of the Binary Outputs
To change the settings of the binary outputs in the Configuration tab, proceed as follows:
In the navigation window, click Binary outputs.
[sc_q100_BO_configuration, 2, en_US]
Figure 3-5
Configure the respective parameters according to the following table.
Table 3-1
Parameter
Source type
Source Type Indication
6
Indication
Source inverted
(can be set individually for all
relay outputs)
Operating mode
(can be set individually for all
relay outputs)
Output time for pulse operating
mode (setting only possible for
operating modes Pulse and
Pulse with retrigger)
Source Type Energy Counter
Energy counter
Energy increase per pulse
Output time for pulse operating
mode
If you select -none- as the source of an indication or energy counter, the corresponding binary output is inactive.
6
7
If you have selected one of the 2 Pulse types in the Operating mode list box, enter an output time x (in x *10 ms) in the Output
time for pulse operating mode field.
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Configuration Tab, Binary Outputs
Settings for Binary Outputs
Default Setting
Indication
-none-
No
Persistent
7
20 (* 10 ms)
-none-
6
1.00 Wh
20 * 10 ms = 200 ms
Setting Range
Indication
Energy counter
Acc. to list box
No
Yes
Persistent
Persistent with fail safe
Pulse
Pulse with retrigger
50 ms to 3 600 000 ms
Acc. to list box
0.10 Wh/VAh/varh to
1 000 000.00 Wh/VAh/varh
50 ms to 3 600 000 ms
Process Connections