Parameter Switching Function For Reverse Operation - YASKAWA CIPR-CR70A Series Technical Manual

Ac drive for cranes 200/400 v class: 0.4 to 110/315 kw
Table of Contents

Advertisement

*1
Set S1-54 to S1-56 = 0 [Disabled] when you do not use the brake sequence.
Note:
• When the 3 motors are used, a protective function set in L1-01 [Motor Overload (oL1) Protection] is applied to motor 1 and motor 2
only. For motor 3, set up a thermal overload relay between the drive and motor 3, so that the sequence trips an external fault (coast to
stop).
• You cannot switch between V/f patterns during run for motor 3. Even when b1-23 = 1 [Selection REV Parameters = Enabled], the
drive will not switch between motors even when the counterweight signal is input.
• If the frequency reference exceeds the maximum output frequency, then it will still be limited by the maximum output frequency set to
each motor. For example, if you set E1-04 = 60 Hz, E3-04 = 50 Hz, d1-04 [Reference 4] = 60 Hz, and d1-04 as the part of multi-step
speed reference, then the frequency reference for motor 1 will be 60 Hz, and 50 Hz for motor 2.
• Refer to the following for the default settings change as the control method.
–Parameters Changed by A1-02 [Control Method Selection] on page 506
–Parameters Changed by E3-01 [Motor 2 Control Mode Selection] on page 509
H1-xx
Setting
Value
16
Motor 2 Selection
39
Motor 3 Selection
Note:
When H1-xx = 16 and/or 39, the drive does not detect oPE08 [Parameter Selection Error] concerning contradictory settings in the
MFDIs, MFDOs, analog inputs, and monitor outputs. The drive recognizes terminals that have not been set to a function as "Not Used".
H2-xx
Setting
Value
1C
Motor 2 Selected
B3
Motor 3 Selection
Related Monitors
No.
MEMOBUS/Modbus Communications Registers
004B(Hex.) bit A
MEMOBUS/Modbus Communications Registers
004B (Hex.) bit C

Parameter Switching Function for Reverse Operation

This function allows the application to switch between the torque compensation delay time, the mid point a
voltage, and the minimum output voltage. The conditions for switching are based on the input terminal status and
the direction of the Run command (forward or reverse), along with the parameter setting combinations.
Set the following parameters when using this function.
• Set b1-23 = 1 [Selection REV Parameters = Enabled].
• Set H1-xx = 38[MFDI Function Selection = Counterweight Selection].
Note:
The switching function is disabled during run.
YASKAWA ELECTRIC SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
Table 3.23 Multi-Funciton Digital Input
Name
Switches between motors 1 and 2.
ON: Selects motor 2
OFF: Selects motor 1
Switches to motor 3. It is necessary to set H1-xx = 16 when setting H1-xx =
39. If H1-xx = 39 is set while H1-xx = 16 is not set, oPE03 [Multi-Function
Input Setting Err] is detected.
ON: Selects motor 3
OFF: Clears the selection of motor 3
Table 3.24 Multi-Function Digital Output
Name
The terminal turns on when motor 2 is selected.
ON: Motor 2 is selected
OFF: Motor 1 is selected
The terminal turns on when motor 3 is selected.
ON: Motor 3 is selected
OFF: Clears the selection of motor 3
1: Motor 2 Selection
1: Motor 3 Selection
3 Startup Procedure and Test Run
Description
Description
Bit
197