Commissioning
Node Name
ProductCode
RevisionCounter
SerialNumber
SoftwareRevision
10.3.3.1.2 Setting Device Parameters
The OPC UA server provides nodes with configuration parameters for the device. For ex-
ample, the OPC UA client can read out the upper limiting value for temperature in the
OverTemperature node.
The path to this node is:
Root > Object > DeviceSet > [device name] > DigitalConnector > Di-
agnostics > Configuration
The following table lists device-specific configuration parameters.
Node Name
CurrentHysteresis
OverTemperature
OverVoltage1L
OverVoltage2L
TemperatureHysteresis
UnderTemperature
UnderVoltage1L
UnderVoltage2L
VoltageHysteresis
10.3.3.1.3 Setting Port Parameters
The OPC UA server provides nodes with configuration parameters for each port.
The path to this node is:
78
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
Node Class
Access
Variable
Read
Variable
Read
Variable
Read
Variable
Read
Node Class
Access Default Description
Variable
Read
10 mA
Variable
Read
70 °C
Variable
Read
30000
mV
Variable
Read
30000
mV
Variable
Read
2 °C
Variable
Read
−25 °C Lower limiting value for the temperature of a port;
Variable
Read
18000
mV
Variable
Read
18000
mV
Variable
Read
300 mV Voltage hysteresis; unit: mA
Description
Product code of the device: "765-xxxx/xxxx-
xxxx"
Hardware version of the device
Serial number of the device
Revision/version of the device firmware
Table 45: Device-Specific Configuration Parameters
Current hysteresis; unit: mA
If the current exceeds the limiting value, the cur-
rent must fall back below the limiting value by the
hysteresis value before the diagnosis is revoked.
Upper limiting value for the temperature of a port;
unit: 0.1 °C
Upper limiting value for the voltage in supply ca-
ble 1; pins with the following functions can be
monitored: L+, DI, DO, DIO, IO-Link; unit: mV
Upper limiting value for the voltage in supply ca-
ble 2; unit: mV
Temperature hysteresis; unit: 0.1 °C
If the temperature exceeds the limiting value, the
temperature must fall back below the limiting
value by the hysteresis value before the diagno-
sis is revoked.
unit: 0.1 °C
Lower limiting value for the voltage in supply ca-
ble 1; pins with the following functions can be
monitored: L+, DI, DO, DIO, IO-Link; unit: mV
Lower limiting value for the voltage in supply ca-
ble 2; unit: mV
If the voltage exceeds the limiting value, the volt-
age must fall back below the limiting value by the
hysteresis value before the diagnosis is revoked.
765-1205/100-000