Power Supply; Table 10 Total Load; Table 11 Power Supply - WAGO 765-1205/100-000 Product Manual

8-channel digital input/output; ethercat; 24 v dc; 2.0 a; 8 × m8 connection
Table of Contents

Advertisement

765-1205/100-000
Property
Voltage drop through high-side path
Self-protection
Maximum capacitive load
Maximum inductive load
Indicators
Diagnostics
Actuator/Sensor Supply
Output voltage
Current
Circuit
Self-protection
Voltage drop through high-side path
Maximum capacitive load
Maximum inductive load
Diagnostics (1L+, 2L+)
Parameters
Maximum total load current (sum of all currents of con-
nections X01–X08)

4.4.4 Power Supply

Parameters
Supply voltage, 1L, 2L
Undervoltage warning, 1L, 2L
Overvoltage warning, 1L, 2L
Module current consumption
Current consumption of supply connections
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
Value
Value (per UL)
Less than 250 mV
Overcurrent, overload, overtemperature and overvolt-
age
100 μF parallel to 12 Ω; 10 Hz
1.15 H / 2 A; 0.2 Hz; DC13 1.15 H / 2 A; 1 Hz; DC13;
Pilot Duty
On/off status LED
Events: overcurrent, overload and overtemperature
24 VDC
Port X01 to X04: 1L powered
Port X05 to X08: 2L powered
Maximum 4.0 A per channel
High-side driver
The 1L+/2L+ output is not resistant to feedback.
The input voltage must not exceed the supply voltage.
Overcurrent, overload, overtemperature and overvolt-
age
Less than 200 mV
1000 µF parallel to 24 Ω; 0.1 Hz
470 µF parallel to 12 Ω; 0.1 Hz
220 µF parallel to 6 Ω; 0.1 Hz
1.15 H / 2 A; 0.2 Hz; DC13 1.15 H / 2 A; 1 Hz; DC13;
Pilot Duty
Events: overcurrent, overload, overtemperature and
overvoltage
Value
Value (per UL)
31.7 A
11.7 A
Value
Value (per UL)
24 VDC, –25 %/+30 %
24 VDC, –25 %/+20 %
(18 VDC ... 31.2 VDC)
(18 VDC ... 28.8 VDC)
Voltages above 34 V can permanently damage the de-
vice.
Voltages below approx. 11 V lead to device reset.
18.0 V (± 5 % at 25 °C) message on
18.3 V (± 5 % at 25 °C) message off
30.0 V (± 5 % at 25 °C) message on
29.7 V (± 5 % at 25 °C) message off
1L: 110 mA (at 24 VDC)
2L: 5 mA (at 24 VDC)
Max. 16 A; ensure external
External fuses in lines 1L
limitation or use fuses in
and 2L: max. 16 A, time-
the cables
delay, min. 30 VDC
Properties
Table 10: Total Load
Table 11: Power Supply
19