Events Triggered By The Io-Link Device; Table 79 Standard Events Of The Io-Link Device - WAGO 765-1205/100-000 Product Manual

8-channel digital input/output; ethercat; 24 v dc; 2.0 a; 8 × m8 connection
Table of Contents

Advertisement

Diagnostics
IO-Link Event Code Description
0x180E
0x180F
0x1810
0x1811
0x1812
0x6000
0x6001
0x6002

11.2.1.11 Events Triggered by the IO-Link Device

Events can also be triggered by an IO-Link device connected to the IO-Link master via a
port. An IO-Link device sends the "Event Code" and the "Event Qualifier" of the event to
the IO-Link master.
The following values are set in the event qualifier:
TYPE = 1 (Notification
MODE = 1 (Single shot)
SOURCE = 0 (Device/remote)
The IO-Link master sends this event to the EtherCAT slave, which can report it to the
EtherCAT master as an emergency. The IODD of the IO-Link device contains manufac-
turer-specific events with message text.
The following table describes possible standard events of the IO-Link device that can trig-
ger EtherCAT emergencies.
IO-Link Event Code Description of the Error Function
0x1000
0x4000
0x4210
0x4220
0x5000
0x5010
0x5011
0x5012
0x5100
0x5101
0x5110
0x5111
0x5112
0x6000
0x6320
0x6321
0x6350
0x7700
110
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
P24 (class B) missing or has under-
voltage
Short circuit on P24 (class B)
Short circuit on I/Q
Short circuit on C/Q
Overcurrent on I/Q
Invalid cycle time
Revision error (incompatible protocol
version)
ISDU batch failed
on the Connected IO-Link Device
General malfunction
Temperature error
Device overheating
Device undercooling
Hardware error in device
Malfunction of a component
Loss of data of non-volatile memory
Batteries too weak
General error in the power supply
Fuse blown/open
Overvoltage in primary power supply
Undervoltage in primary power supply Check tolerance
Error in additional power supply
Error in device software
Parameter error
Missing parameter(s)
Parameter change
Wire break on a lower-level device
765-1205/100-000
Remedy
Check power supply
Check wiring (e.g., 2L+)
Check wiring
Check wiring
Check load
Check port configuration parameters
Check port configuration parameters
Fix parameter inconsistency
Table 79: Standard Events of the IO-Link Device
Corrective Action on the Connected
IO-Link Device
IO-Link device reports unknown error
Eliminate overload
Eliminate heat source
Insulate IO-Link device
Replace IO-Link device
Repair for replacement
Check batteries
Replace batteries
Check availability
Replace fuse
Check tolerance
Check tolerance
Check firmware version
Check datasheet and values
Check datasheet
Check configuration
Check installation

Advertisement