3 Utility Function Mode
3.3.18 Multiturn Limit Value Setting Change When a Multiturn Limit Disagreement Alarm (A.CC0)
Occurs (Fn013)
(4)
Operation Example
Step
1
2
3
4
3-50
Display Example
− F U N C T I O N −
A . C C 0
F n 0 1 2 : S o f t V e r
F n 0 1 3 : M t u r n L m S e t
F n 0 1 4 : O p t I n i t
F n 0 1 B : V i b l v l I n i t
A . C C 0
M u l t i t u r n L i m i t
S e t
S t a r t
: [ D A T A ]
R e t u r n : [ S E T ]
D o n e
M u l t i t u r n L i m i t
S e t
S t a r t
: [ D A T A ]
R e t u r n : [ S E T ]
− F U N C T I O N −
A . C C 0
F n 0 1 2 : S o f t V e r
F n 0 1 3 : M t u r n L m S e t
F n 0 1 4 : O p t I n i t
F n 0 1 B : V i b l v l I n i t
Description
Press the
Key to open the Utility Func-
tion Mode main menu, and select Fn013 using
the
or
Key.
Press the
Key.
The display is switched to the setting display
of Fn013 (Multiturn Limit Value Setting
Change When a Multiturn Limit Disagree-
ment Alarm (A.CC0) Occurs).
Note: If the display is not switched and "NO-
OP" is displayed in the status display,
the Write Prohibited Setting (Fn010 =
0001) is set. Check the setting and
reset.
Press the
Key to set the multiturn limit
value.
When the setting is completed, "Done" is dis-
played in the status display. Turn the power
OFF then ON to update the multiturn limit
setting.
Note: If the
Key is pressed instead of
the
Key, the multiturn limit
value will not be reset.
Press the
Key.
The display returns to the Utility Function
Mode main menu.