ABB SACE Emax Instructions For Installation And Service page 50

Hide thumbs Also See for SACE Emax:
Table of Contents

Advertisement

Dimensione della cella
A
E1-A
400/15,7''
E2-A
400/15,7''
E3-A
500/19,7''
E4-A
700/25,7''
E6-A
1000/39,3''
Adatto per operare al 100% della corrente in un cubicolo delle dimen-
sioni riportate in figura, con una ventilazione di 48 pollici quadri (12x4)
nella parte inferiore e nella parte superiore (**).
Fare riferimento ai disegni del cubicolo per le verifiche.
Fig. 45
Mod.
M4379
Rev.
Courtesy of NationalSwitchgear.com
Dimensions of compartment
Suitable for continuos operation at 100% rating in a minimum cubicle
space (see the table), with a ventilation of 48 (12x4) sq. in. side bottom
and side top (**).
Refer to shop drawings for verification.
Apparecchio
SACE Emax
Apparatus
N° Doc.
601933/004
Doc. No.
Scala
Scale
N° Pag.
Sh. No.
48/96