Function setting switch setting
Set the following functions using the function setting switch on the front of I/O module.
• Network setting function
• Input response time setting function
• Output HOLD/CLEAR setting function
The setting of function setting switch is enabled when the I/O module is powered on. Thus, set each function when the module
is powered off.
When operating the function setting switch, use a flathead screwdriver having a blade of 1.2mm or less in
width.
Setting procedure
Set each function with the function setting switch 1 to 10.
Switch name
Function setting switch 1
Function setting switch 2 to 4
Function setting switch 5
Function setting switch 6 to 7
Function setting switch 8 to 9
Function setting switch 10
Do not change any function setting switch while the I/O module is powered on. If the setting of a function
setting switch is changed while the I/O module is powered on, one of the errors from function setting switch 1
changed error (error code: 0201H) to function setting switch 10 changed error (error code: 020AH) occurs,
and the changed setting of that function setting switch is not applied. Returning the function setting switch to
its previous position and turning on Error clear request flag (RWw0.b10) eliminate the error.
6 INSTALLATION AND WIRING
60
6.2 Setting Switch
Function name
Network setting function
Input response time setting
function
Output HOLD/CLEAR setting
function
Use prohibited
Use prohibited
Use prohibited
Setting details
Set this switch to OFF in normal operation.
Set it to ON to perform a unit test. ( Page 94 Unit Test)
Set the input response time. ( Page 76 Setting procedure)
Set output HOLD/CLEAR. ( Page 77 Setting procedure)
Fix these switches to OFF.
Fix these switches to OFF.
Fix this switch to OFF.