Device Range That Can Be Set - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

9.6 Device Range that Can Be Set

The device ranges of controller that can be used for GOT
are as follows.
Note that the device ranges in the following tables are the
maximum values that can be set in GT Designer3.
The device specifications of controllers may differ
depending on the models, even though belonging to the
same series.
Please make the setting according to the specifications of
the controller actually used.
When a non-existent device or a device number outside
the range is set, other objects with correct device settings
may not be monitored.
Setting item
Item
Set the device name, device number, and bit number.
Device
The bit number can be set only when specifying the bit
of word device.
Displays the device type and setting range which are
Information
selected in [Device].
POINT
POINT
POINT
(1) Device settings of SHARP PLC
(a) When setting a register as a bit device
• Registers
Set the type (first 2 digits) and the address.
Number
• File register
Set the file number and the address.
File number
Description
Address
Address
(b) When setting a register and memory as a
word device.
• I/O relay
Set a combination of the device address
(multiple of 16)+bit address format (fixed to
0).
Even number
• Registers and file register
Set the device address (multiple of 16).
Type
(2) Monitoring the timer (T) and the counter (C)
(a) Address setting
Be sure not to set the same address range for
the timer (T) and the counter (C).
Even if these addresses are overlapped, GOT
displays no error.
GOT monitors them according to the address
instead of the device name.
Therefore, if a device which is invalid for the
SHARP PLC side parameter is set using GT
Designer3, GOT monitors other device (a
device corresponding to the address range of
the set device).
Example:
Content in SHARP PLC parameter setting
T0000 to T1000
C1001 to C1777
Content in GT Designer3
parameter setting
(b) Contact writing into timer (T) and the counter
(C)
Writing the contact for the timer (T) and the
counter (C) can only be done while the CPU is
in RUN (while the timer and counter is in
operation).
9. CONNECTION TO SHARP PLC
9.6 Device Range that Can Be Set
10
The next line mu
to 0,for it is bit ad
11
Even number
12
13
14
Even if GT Designer3 is
set to "C0000", GOT will
also monitor "T0000".
15
9 - 15
9