Mitsubishi Electric GOT1000 Series Connection Manual page 364

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

11.5.10 Connecting to KE3000
Key Lock setting
To write the Digital and the Analog parameters, set the
Key Lock setting.
Communication settings
Make the communication settings by operating the
switches SW2 and SW3 of the module.
SW3 SW2
Printed wiring board
in main body
(1) Setting by SW2
Item
*2
MODBUS RTU
Transmission code
9600bps
*1
Transmission speed
19200bps
Transmission character
8bits, None, 1bit (fixed)
*2
structure
*1
Adjust the settings with GOT settings.
*2
When the transmission code is MODBUS RTU, the setting of
the transmission character structure is fixed.
(2) Setting by SW3
Set the station No. as follows.
SW3-4
SW3-5
SW3-6
SW3-7
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
*1
Avoid duplication of the station No. with any of the other
units.
11 - 30
11. CONNECTION TO CHINO CONTROLLER
11.5 Controller Side Setting
Front panel
Set value
SW2-2
SW2-3
OFF
-
-
-
*1
SW3-8
Station No.
OFF
1
OFF
1
OFF
2
OFF
3
:
:
ON
29
ON
30
ON
31
11.5.11 Connecting to LE5000
Key Lock setting
To write the Digital and the Analog parameters, set the
Key Lock setting.
Communication settings
Set the communication settings with controller key
operation.
Item
RTU/ASCII
*1
Station No.
Transmission speed
*2
Character
(Bit length, Parity bit, Stop bit)
-
*1
Avoid duplication of the station No. with any of the other
units.
OFF
*2
Adjust the settings with GOT settings.
ON
-
Set value
RTU
1 to 99
*2
9600bps, 19200bps
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
[8E1]: 8bit, Even, 1bit
[8E2]: 8bit, Even, 2bit
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit