Mitsubishi Electric GOT1000 Series Connection Manual page 210

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

Ethernet setting
Item
The host is displayed. (The
Host
host is indicated with an
asterisk (*).)
Set the network No. of the
N/W No.
connected Ethernet module.
(Default: blank)
Set the station No. of the
*1
connected Ethernet module.
PLC No.
(Default: blank)
Type
OMRON (fixed)
Set the IP address of the
IP Address
connected Ethernet module.
(Default: blank)
Set the port No. of the
Port No.
connected Ethernet module.
(Default: 9600)
Select a communication
Communication format
protocol. (Default: UDP)
*1
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
 Communication detail settings
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
User's Manual of GOT used.
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
4 - 38
4. CONNECTION TO OMRON PLC
4.3 Ethernet Connection
Description
Set value
-
1 to 127
1 to 254
OMRON
(fixed)
PLC side IP
address
256 to 65534
UDP, TCP