Setting item
The following describes the setting items for the standard I/F setting and extension I/F setting.
Item
Standard I/F Setting
CH No.
I/F
Driver
Detail Setting
RS232 Setting
1 - 12
1. PREPARATORY PROCEDURES FOR MONITORING
1.1 Setting the Communication Interface
Set channel No. and drivers to the GOT standard interfaces.
GT16, GT14, GT12: Standard I/F-1, Standard I/F-2, Standard I/F-3, Standard I/F-4
GT15, GT1030, GT1020: Standard I/F-1, Standard I/F-2
GT11, GT105 , GT104 : Standard I/F-1, Standard I/F-2, Standard I/F-3
Set the CH No. according to the intended purpose.
The number of channels differs depending on the GOT to be used.
0: Not used
1 to 4: Used for connecting a controller of channel No. 1 to 4 set in Setting connected equipment (Channel
setting)
8: Used for barcode reader connection, RFID connection, PC remote operation connection, fingerprint
authentication device connection, printer (serial), or GOT (extended computer)
9: Used for connecting Host (PC)
*: Used for gateway function, MES interface function, and Ethernet download
Multi: Used for Ethernet multiple connection
The communication type of the GOT standard interface is displayed.
Set the driver for the device to be connected.
None
Host (PC)
Each communication driver for connected devices
Make settings for the transmission speed and data length of the communication driver.
Refer to each chapter of the equipment to be connected to the GOT.
To validate the 5V power supply function in RS232, mark the [Enable the 5V power supply] checkbox.
The RS232 setting is invalid in the following cases.
• CH No. of [I/F-1: RS232] is [9] in GT15 and 16.
• CH No. of [I/F-1: RS232] is [9] or [8] in GT14.
• For GT12, GT11 and GT10
Description