11.5.13 Station number setting
Set each station number so that no station number
overlaps.
The station number can be set without regard to the cable
connection order. There is no problem even if station
numbers are not consecutive.
Station
Station
No.3
No.7
GOT
Examples of station number setting
(1) Direct specification
When setting the device, specify the station number of
the controller of which data is to be changed.
Model name
LT230, LT300, LT400, LT830
DZ1000, DZ2000
DB1000, DB2000
GT120
KP1000, KP2000
AL3000, AH3000
SE3000
JU
KE3000
LE5000
(2) Indirect specification
When setting the device, indirectly specify the station
number of the controller of which data is to be changed
using the 16-bit GOT internal data register (GD10 to
GD25).
When specifying the station No. from 100 to 115 on GT
Designer3, the value of GD10 to GD25 compatible to
the station No. specification will be the station No. of
the controller.
Specification
Compatible
station NO.
device
100
GD10
101
GD11
102
GD12
103
GD13
104
GD14
1 to 99: LT230, LT300, LT400, LT830
105
GD15
106
GD16
107
GD17
1 to 31: DZ1000, DZ2000, AL3000
108
GD18
1 to 95: GT120
109
GD19
For the setting other than the above, error
110
GD20
(dedicated device is out of range) will occur.
111
GD21
112
GD22
113
GD23
114
GD24
115
GD25
11 - 32
11. CONNECTION TO CHINO CONTROLLER
11.5 Controller Side Setting
Station
Station
Station
No.1
No.15
No.6
Specification
Refer to
range
11.5.1
1 to 99
11.5.2
1 to 31
11.5.3
1 to 99
11.5.4
1 to 95
11.5.5
1 to 99
11.5.6
1 to 31
11.5.7
1 to 31
11.5.8
1 to 99
11.5.9
1 to 31
11.5.10
1 to 99
11.5.11
Setting range
DB1000, DB2000, KP1000,
KP2000, JU, LE5000
AH3000, KE3000, SE3000
(3) All station specification
Target station differs depending on write-in operation or
read-out operation.
• For write-in operation, all station will be a target.
• For read-out operation, only one station will be a
target.
• All station specification is not available for KE3000.
Do not use the all station specification for systems
which include KE3000.