15.4 GOT Side Settings
15.4.1 Setting communication
interface (Communication
settings)
Set the channel of the equipment to be connected to the
GOT.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Panasonic
• Controller Type: Panasonic MEWNET-FP
• I/F: Interface to be used
• Driver: Panasonic MEWNET-FP
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
15.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
15 - 18
15. CONNECTION TO PANASONIC INDUSTRIAL DEVICES SUNX PLC
15.4 GOT Side Settings
3.
4.
Click!
[Controller Setting] from the
15.4.2 Communication detail settings
Make the settings according to the usage environment.
Item
Description
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 9600bps)
Set this item when change the data
length used for communication with
Data Bit
the connected equipment.
(Default: 8bits)
Set the number of retries to be
performed when a communication
timeout occurs.
Retry
When receiving no response after
retries, the communication times out.
(Default: 0time)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Specify the host address (station No.
of the PLC to which the GOT is
Host Address
connected) in the network of the GOT.
(Default: 1)
Set this item to adjust the
transmission timing of the
Delay Time
communication request from the
GOT.
(Default: 0ms)
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication Settings]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
User's Manual of GOT used.
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
0 to 5times
3 to 30sec
1 to 31
0 to 300 (ms)