Mitsubishi Electric GOT1000 Series Connection Manual page 280

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

7.5.7
Connecting to D0-DCM
Communication settings
Write the following communication settings to the
specified register using the programmer.For details of
the register, refer to the following manual.
KOYO EI PLC user's Manual
Item
Transmission mode
HEX
Protocol
DirectNet
Station No.
1 to 90
9600bps, 19200bps, 38400bps, 57600bps,
*1
Transmission speed
115200bps
NONE, ODD,
Parity
EVEN (Only communication port 2)
RTS On Delay Time
0ms
(Only communication port 2)
RTS Off Delay Time
0ms
(Only communication port 2)
Timeout
800ms/960ms/1200ms/1600ms/4000ms/
(Only communication port 2)
8000ms/16000ms/40000ms
485 mode selection
RS232, RS422/485 4 line type
(Only communication port 2)
Data bit
8bits, 7bits
(Only communication port 2)
Stop bit
1bit, 2bits
(Only communication port 2)
The timeout between
characters
0 to 9999ms
(Only communication port 2)
The completion of a
Default use,A preset value is effective
setting
Reset timeout
Invalid,Effective
*1
Indicates only the transmission speeds that can be set on
the GOT side.
Set the same transmission speed of the GOT.
For the transmission speed setting on the GOT side, refer to
the following.
7.4.1 Setting communication interface
(Communication settings)
7 - 26
7. CONNECTION TO KOYO EI PLC
7.5 PLC Side Setting
Set value
7.5.8
Connecting to D2-DCM
Communication settings
Make the following settings using the programmer.
Item
Station No.
1 to 90
*1
9600bps, 19200bps, 38400bps
Transmission speed
Data bit
8bits (Fixed)
Stop bit
1bit (Fixed)
Parity
NONE, ODD
Self-diagnostic mode
OFF
Response delay time
0ms
Peer to Peer
OFF
Master/Slave
Slave
Timeout
Enable
Transmission mode
HEX
MODBUS
OFF
*1
Indicates only the transmission speeds that can be set on
the GOT side.
Set the same transmission speed of the GOT.
For the transmission speed setting on the GOT side, refer to
the following.
7.4.1 Setting communication interface
(Communication settings)
7.5.9
Station No. settings
Set each station number so that no station number
overlaps.
The station number can be set without regard to the cable
connection order. There is no problem even if station
numbers are not consecutive.
Station No.3
GOT
The example of a Station No. setting
(1) Direct specification
Specify the station No. of the PLC to be changed when
setting device.
Specification range
1 to 90
Set value
Station No.1
Station No.15