Mitsubishi Electric GOT1000 Series Connection Manual page 423

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

15.5 PLC Side Setting
POINT
POINT
POINT
Panasonic Industrial Devices SUNX PLC
For details of the Panasonic Industrial Devices SUNX
PLC, refer to the following manual.
Panasonic Industrial Devices SUNX PLC user's
Manual
Connecting to the tool port of the PLC CPU
Item
*1
Transmission speed
Data bit
Stop bit
Parity bit
Modem connection
Module No.
*1
Indicates only the transmission speeds that can be set on
the GOT side.
Set the same transmission speed of the GOT.
For the transmission speed setting on the GOT side, refer to
the following.
15.4.1 Setting communication interface
(Communication settings)
The setting range varies with the connected PLC.
Connecting to the RS232C and COM port of
the PLC CPU
Item
*1
Transmission speed
Data bit
Stop bit
Parity bit
Modem connection
*2
Serial port action selection
Module No.
*1
Indicates only the transmission speeds that can be set on
the GOT side.
Set the same transmission speed of the GOT.
For the transmission speed setting on the GOT side, refer to
the following.
15.4.1 Setting communication interface
(Communication settings)
The setting range varies with the connected PLC.
*2
Set when connecting to FP0, FP1, FP2 or FP-M.
Set value
4800bps, 9600bps, 19200bps,
38400bps, 57600bps, 115200bps
7bit, 8bit
1bit
Odd
No
1
Set value
4800bps, 9600bps, 19200bps,
38400bps, 57600bps, 115200bps
7bit, 8bit
1bit
Odd
No
1 (Computer link)
1
15. CONNECTION TO PANASONIC INDUSTRIAL DEVICES SUNX PLC
Connecting to the computer communication
unit
Item
*1
Transmission speed
Data bit
Stop bit
Parity bit
Parity check
Control signal
*1
Indicates only the transmission speeds that can be set on
the GOT side.
Set the same transmission speed of the GOT.
For the transmission speed setting on the GOT side, refer to
the following.
15.4.1 Setting communication interface
(Communication settings)
The setting range varies with the connected PLC.
Connecting to the communication cassette
(1) Communication settings
Set the commnumication settings for the COM 1 port
and COM2 port to connect GOT.
Item
Communication mode
*1
Transmission speed
Modem connection
Data bit
Parity check
Stop bit
Unit No.
*2
Port selection
*1
Indicates only the transmission speeds that can be set on
the GOT side.
Set the same transmission speed of the GOT.
For the transmission speed setting on the GOT side, refer to
the following.
15.4.1 Setting communication interface
(Communication settings)
*2
Set the COM2 port only.
(2) Switch setting on the Communication cassette
(AFPX-COM3)
Set the switch on the back.
Switch No.
Setting
1
OFF
2
OFF
3
OFF
4
OFF
15.5 PLC Side Setting
Set value
4800bps, 9600bps, 19200bps
7bit, 8bit
1bit
Odd
Yes
Invalidate CS, CD
Set value
Computer link
4800bps, 9600bps, 19200bps,
38400bps, 57600bps, 115200bps
No
7bit, 8bit
Odd
1bit
1
Communication cassette
Setting details
O
1
N
RS422
2
3
Terminating resistor
4
OFF
15 - 19
9
10
11
12
13
14
15