11.3 Connection Diagram
The following diagram shows the connection between the
GOT and the PLC.
11.3.1
RS-232 cable
Connection diagram
RS232 connection diagram 1)
GOT side
CD
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
-
9
FG
-
*1
Terminal number of the controller and the converter differ
depending on the model.Refer to the following table.
Controller
DZ1000,
Signal
LT300
LT400
DZ2000
name
Terminal
Terminal
Terminal
No.
No.
SD
11
11
RD
13
13
SG
15
15
KP1000
KP2000
Signal
name
Terminal No.
Terminal
No.
*2
*2
*2
R
, B
, C
SD
13
27
RD
12
26
SG
14
28
*1
For KP2000 series, the terminal No. differs according to the
model.
*2
This indicates the symbols of the position 10) (third zone) of
the following models.
Model: KP2 4) 5) 6) 7) 8) 9) 10) – 12) 13) 14)
For the symbol B, two terminal numbers are available. Select
as necessary.
11 - 10
11. CONNECTION TO CHINO CONTROLLER
11.3 Connection Diagram
CHINO controller
side, Interface
converter
-
SD
RD
-
SG
Converter
DB1000
DB2000
SC8-10
Terminal
Terminal
Terminal
No.
No.
No.
19
13
27
21
12
26
23
14
28
Controller
AL3000
SE3000
AH3000
*1
Terminal
Terminal
name
name
*2
*2
*2
, D
B
, E
30
SD
29
RD
31
SG
Precautions when preparing a cable
(1) Cable length
The length of the RS-232 cable must be 15m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(3) CHINO controller side connector
Use the connector compatible with the CHINO
controller side module.
For details, refer to the user's manual of the CHINO
controller.
No.
2
1
3
SD
RD
SG