3.4 GOT Side Settings
3.4.1
Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Azbil
• Controller Type: Set as follows.
<When connecting to DMC50 and AHC2001>
Azbil DMC50
<When connecting to a module other than above>
Azbil SDC/DMC
• I/F: Interface to be used
• Driver: Azbil SDC/DMC
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
3.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
3 - 46
3. CONNECTION TO AZBIL CONTROL EQUIPMENT
3.4 GOT Side Settings
Click!
[Controller Setting] from the
3.4.2
Communication detail settings
3.
4.
Item
Transmission
Speed
Data Bit
Stop Bit
Parity
Retry
Timeout Time
*3*4
Host Address
Delay Time
*2
Format
*1
Do not specify "0".
*2
Format is ignored when connecting to DMC50.
*3
Host Address is ignored when connecting to DMC10 or SDC.
*4
Host Address is valid when connecting to DMC50.
Devices to be the target of Host Address setting differ
depending on the system configuration.
<When connecting to the temperature controller via COM
module>
Specify the station No. of the COM module.
<When connecting to the temperature controller directly>
Specify the station No. of the temperature controller.
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 9600bps)
Set this item when change the data
length used for communication with
the connected equipment.
(Default: 8bits)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
during communication.
(Default: Even)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 0time)
Set the time period for a
communication to time out.
(Default: 3sec)
Specify the host address (station No.
of the GOT to which the temperature
controller is connected) in the
connected network.
(Default: 1)
Set this item to adjust the
transmission timing of the
communication request from the
*1
GOT.
(Default: 1ms)
Select the communication format.
(Default: 1)
format 1: only continuous access
format 2: continuous and random
access
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
3 to 30sec
1 to 15
0 to 300ms
1/2