6.3 Ethernet Connection

6.3.1
Connecting to KV-700/1000/3000/5000/5500
Ethernet
CPU
module
PLC
Ethernet
Series
*4
module
KV-5000
-
Twisted pair cable
• 10BASE-T
Shielded twisted pair cable (STP) or
unshielded twisted pair cable (UTP):
Category 3, 4, and 5
• 100BASE-TX
KV-700
Shielded twisted pair cable (STP):
KV-1000
KV-LE20V
Category 5 and 5e
KV-3000
KV-LE21V
KV-5000
KV-5500
*1
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver or other system equipment corresponding to the applicable Ethernet network
system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standards.
*2
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*3
When connecting GT16 of the function version A to an equipment that meets the 10BASE (-T/2/5) standard, use the switching
hub and operate in a 10Mbps/100Mbps mixed environment.
For how to check the function version, refer to the following.
*4
Product manufactured by KEYENCE CORPORATION. For details of the product, contact KEYENCE CORPORATION.
*5
GT14 models compatible with Ethernet connection are only GT1455-QTBDE, GT1450-QMBDE and GT1450-QLBDE.
Connection cable
Connection cable
Cable model
segment length
GT16 User's Manual
GOT
GOT
Maximum
Option device
*2
- (Built into GOT)
100m
GT15-J71E71-100
- (Built into GOT)
100m
GT15-J71E71-100
6. CONNECTION TO KEYENCE PLC
6.3 Ethernet Connection
Communication driver
Ethernet (KEYENCE), Gateway
Number of connectable
equipment
*3
Model
When PLC:GOT is N:1
The following shows the
*5
number of PLCs for 1 GOT
<For GT16, GT14>
TCP: 128 or less
UDP: 128 or less
<For GT15, GT12>
TCP: 10 or less
UDP: 128 or less
*5
When PLC:GOT is 1:N
The following shows the
number of GOTs for 1 PLC
TCP: 15 or less
UDP: 1 or less
6 - 17