Mitsubishi Electric GOT1000 Series Connection Manual page 236

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

6.2.2
Connecting to KV-3000
When connecting to a PLC
KV-3000
PLC
Model
Communication
name
Type
KV-3000
RS-232
*1
The cable and conversion connector are products manufactured by KEYENCE CORPORATION.
For details of the product, contact KEYENCE CORPORATION.
6 - 4
6. CONNECTION TO KEYENCE PLC
6.2 Serial Connection
Connection cable
Connection cable
Cable model
Connection diagram number
GT09-C30R21101-6P
or
RS232 connection diagram
1)
RS232 connection diagram
4)
*1
OP-26487
GOT
Conversion
Max.
Option device
*1
distance
connector
- (Built into GOT)
-
15m
GT15-RS2-9P
-
15m
- (Built into GOT)
- (Built into GOT)
OP-26486
2.5m
GT15-RS2-9P
Communication driver
KEYENCE KV-700/1000
GOT
Number of
connectable
Model
equipment
1 GOT for 1 PLC

Advertisement

Table of Contents
loading