*1
Click the [Setting] button and perform the setting in the [GOT
IP Address Setting] screen.
*2
By setting of the OMRON PLC, set the same [GOT
Communication Port No.] setting as that of [FINS UDP Port ]
of CX-Programmer.
*3
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
 Ethernet setting
(2) GT15, GT12
Item
Set the network No. of the
GOT NET No.
GOT.
(Default: 1)
Set the station No. of the GOT.
*2
GOT PLC No.
(Default: 1)
Set the IP address of the GOT.
GOT IP Address
(Default: 192.168.0.18)
Set the subnet mask for the
sub network. (Only for
connection via router) If the
Subnet Mask
sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the
Default Gateway
GOT is connected. (Only for
connection via router)
(Default: 0.0.0.0)
Set the GOT port No. for
Ethernet Download
Ethernet download.
Port No.
(Default: 5014)
Set the GOT port No. for the
GOT Communication
connection with the Ethernet
*1
module.
Port No.
(Default: 5018)
Set the number of retries to be
performed when a
communication timeout
Retry
occurs.When receiving no
response after retries, the
communication times out.
(Default: 3times)
Specify the time period from
the GOT startup until GOT
Startup Time
starts the communication with
the PLC CPU. (Default: 3sec)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Set the delay time for reducing
the load of the network/
Delay Time
destination PLC. (Default:
0ms)
*1
By setting of the OMRON PLC, set the same [GOT
Communication Port No.] setting as that of [FINS UDP Port ]
of CX-Programmer.
*2
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
 Ethernet setting
4. CONNECTION TO OMRON PLC
4.3 Ethernet Connection
Description
Range
1 to 127
1 to 254
0.0.0.0 to
255.255.255.
255
0.0.0.0 to
255.255.255.
255
0.0.0.0 to
255.255.255.
255
1024 to 5010,
5014 to
65534
(Except for
5011, 5012,
5013 and
49153)
1024 to 5010,
5014 to
65534
(Except for
5011, 5012,
5013 and
49153)
0 to 5times
3 to 255sec
3 to 90sec
0 to 10000
( 10ms)
4 - 37