4.3.2
GOT side settings
Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: OMRON
• Controller Type: OMRON SYSMAC CS/CJ
• I/F: Interface to be used
• Driver: Ethernet (OMRON), Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
4.3.2
Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
4 - 36
4. CONNECTION TO OMRON PLC
4.3 Ethernet Connection
Click!
[Controller Setting] from the
Communication detail settings
Make the settings according to the usage environment.
(1) GT16, GT14
3.
4.
Item
GOT NET No.
*3
GOT PLC No.
GOT IP Address
*1
Subnet Mask
Default Gateway
Ethernet Download
*1
Port No.
GOT Communication
*2
Port No.
Retry
Startup Time
Timeout Time
Delay Time
Description
Set the network No. of the
GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 1)
Set the IP address of the GOT.
*1
(Default: 192.168.3.18)
Set the subnet mask for the
sub network. (Only for
connection via router) If the
sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the
*1
GOT is connected. (Only for
connection via router)
(Default: 0.0.0.0)
Set the GOT port No. for
Ethernet download.
(Default: 5014)
Set the GOT port No. for the
connection with the Ethernet
module.
(Default: 5018)
Set the number of retries to be
performed when a
communication timeout
occurs. When receiving no
response after retries, the
communication times out.
(Default: 3times)
Specify the time period from
the GOT startup until GOT
starts the communication with
the PLC CPU. (Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing
the load of the network/
destination PLC. (Default:
0ms)
Range
1 to 127
1 to 254
0.0.0.0 to
255.255.255.
255
0.0.0.0 to
255.255.255.
255
0.0.0.0 to
255.255.255.
255
1024 to 5010,
5014 to
65534
(Except for
5011, 5012,
5013 and
49153)
1024 to 5010,
5014 to
65534
(Except for
5011, 5012,
5013 and
49153)
0 to 5times
3 to 255sec
3 to 90sec
0 to 10000
( 10ms)