5.3 Connection Diagram
The following diagram shows the connection between the
GOT and the PLC.
5.3.1
RS-232 cable
Connection diagram
RS232 connection diagram 1)
GOT side
-
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
NC
9
FG
-
RS232 connection diagram 2)
GOT side
-
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
NC
9
FG
-
5 - 6
5. CONNECTION TO OMRON TEMPERATURE CONTROLLER
5.3 Connection Diagram
OMRON temperature
controller side
SG
13
SD
11
RD
12
Interface converter (K3SC-10)
SG
3
RD
6
SD
5
Precautions when preparing a cable
(1) Cable length
The length of the RS-232 cable must be 15m or less
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(3) OMRON temperature controller side connector
Use the connector compatible with the OMRON
temperature controller.
For details, refer to the user's manual of the OMRON
temperature controller.