Mitsubishi Electric GOT1000 Series Connection Manual page 136

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

3.3 Connection Diagram
The following diagram shows the connection between the
GOT and the control equipment.
3.3.1
RS-232 cable
Connection diagram
RS232 connection diagram 1)
GOT side
-
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
NC
9
FG
-
*1
For details on the setting method of the TERMINAL mode,
refer to the following.
3.5.5 Connecting to CMC10L
RS232 connection diagram 2)
GOT side
-
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
NC
9
FG
-
*1
Pin No. of temperature controller differs depending on model and optional function model.
Refer to the following table. The numbers in ( ) of the following table correspond to optional function models.
SDC20
Signal name
(03, 05)
Pin No.
Pin No.
SG
5
SD
17
RD
18
3 - 22
3. CONNECTION TO AZBIL CONTROL EQUIPMENT
3.3 Connection Diagram
Interface converter(CMC10L) * 1
8
3
2
7
5
Temperature
controller side
SG
SD
RD
Model of temperature controller
SDC21
SDC40A, SDC40B, SDC40G
(10)
(04, 07, 09)
Pin No.
18
29
16
27
17
28
Precautions when preparing a cable
(1) Cable length
The length of the RS-232 cable must be 15m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(3) AZBIL control equipment side connector
Use the connector compatible with the AZBIL control
CS
equipment side module.
For details, refer to the user's manual of the AZBIL
SD
control equipment
RD
RS
SG
* 1
CPU module
Pin No.
61
60
59
AHC2001
SCU module
Pin No.
Pin No.
5
5
3
3
2
2

Advertisement

Table of Contents
loading

Table of Contents