Nanoline
86
PHOENIX CONTACT
Holding register 0x0109: Communications watchdog timer (ModScan32 address:
40265)
0 to 999.9 seconds in BDC format. For example, a register value of 0x0150 provides a
watchdog time of 15.00 seconds
15
14
7
6
Holding register 0x010A: Response timeout count (ModScan32 address: 40266)
This register specifies the SPI Response Timeout in milliseconds
15
14
7
6
A 2
Modbus/Nanoline communication
Table A-1
Modbus function codes
Modbus
Modbus commands allowed
reference type
Coils
Read Coil Status
Write Single Coil
Write Multiple Coils
Discrete inputs
Read Discrete Inputs
Input registers
Read Input Register
Holding
Read Holding Registers
registers
Write Single Register
Write Multiple Registers
Read/Write Multiple Registers
*
These commands will not function if the serial port configuration for Modbus RTU
or the COM interface configuration for Modbus TCP are set to Read Only in
nanoNavigator.
The ModScan32 request address range is shown in decimal only. The ModScan32
software does not start its addressing at 0 so all decimal ranges shown are offset by a factor
of one, i.e. hexadecimal 0x1000 is the equivalent of decimal 4096, but because of
ModScan32 addressing, the starting address is actually 4097. If using ModScan32 in the
hexadecimal format, then hexadecimal 0x1000 actually equals 0x1001.
13
12
11
5
4
3
13
12
11
5
4
3
*
*
*
*
*
10
9
2
1
10
9
2
1
Function
Access
code
01
Bit
05
Bit
15
Bit
02
Bit
04
Word
03
Word
06
Word
16
Word
23
Word
2338_en_O
8
0
8
0