Nanoline Base Unit; I/O Expansion Modules; Nanoline Base Unit Type Codes - Phoenix Contact Nanoline Series User Manual

Table of Contents

Advertisement

Nanoline
6
PHOENIX CONTACT
nLC-050-024D-06I-04QRD-05A
Product Family
Type
Power Supply Voltage
024 = 24 volts
100 = 100-240 volts
Power Supply Type
A = AC
D = DC
X = AC/DC
Figure 1-2

Nanoline base unit type codes

1.1.1

Nanoline base unit

The base unit contains the processing capability of the Nanoline system. One base unit is
required for each Nanoline control system. Power connections are made to the base unit
and distributed to the various modules from the base unit. The base unit also contains
connection points (terminals) for the input and output devices that are controlled or
monitored.
NLC-05...
A maximum of three I/O expansion modules can be attached to a base unit.
Two option slots are available on the base unit to install base unit option modules. D-SUB 9
connectors are located on each side of the unit. The left-side connector is for
communication expansion modules, and the right-side connector is for I/O expansion
modules. Both connectors are female to prevent improper module connection.
The power requirements and input/output (I/O) mix determine the model of base unit used.
NLC-03...
The NLC-03... base unit has an integrated RJ12 connector as a connection point for
programming, RS-232 or RS-485 2-wire communication. D-SUB 9 connectors are located
on each side of the base unit. The left-side connector is for communication modules and the
right-side connector allows connection of one NLC-IOX... expansion module.
1.1.2

I/O expansion modules

In addition to the I/O points located on the base unit, I/O expansion modules (NLC-IO-...)
can be connected to the base unit to provide additional connection points. Different I/O
modules provide different combinations and types of I/O.
Max Output Current*
00 = less than 1 amp
01 = 1 amp or less
05 = 5 amps or less
Output Type*
TN = Transistor, NPN
TP = Transistor, PNP
TX = Transistor, PNP and NPN
RD = Relay, DC
RA = Relay, AC
RX = Relay, AC or DC
Number of Digital Outputs*
Number of Digital Inputs*
* optional component