Digital inputs
Number
Connection method
Input design
Nominal input voltage
Input voltage range "0" signal
Input voltage range "1" signal
Nominal input current ON
Nominal input current OFF
Response time ON
Response time OFF
Protection
Permissible cable length to sensor
High speed counter, square wave (minimum pulse width of 60 µs)

Digital outputs

Output type
Number
Nominal power supply V
N
Connection method
Maximum switching voltage @ V
Minimum switching voltage @ V
Maximum switching voltage
Maximum switching current
Maximum current per channel
Maximum current per module
Differential voltage
Nominal load
Ohmic
Lamp
Inductive
Motor inrush current
Motor full load current
Signal delay @ 20°C (excluding bounce)
Release time @ 20°C (excluding bounce)
Mechanical service life
Electrical service life (see Figure D-1)
Operating frequency
No load
Rated load
Overload response
Protection
106
PHOENIX CONTACT
N
N
2701027
2701030
6
Screw terminal, 0.2 - 2.5 mm², 12-24 AWG, 0.5-0.6 Nm
EN 61131-2 Type 1 (NPN or PNP)
24 V DC
0...5 V
15...30 V
5 mA DC
1 mA
60 µs
70 µs
Polarity reversal
2701027
2701030
PNP
NPN
transistor
transistor
24 V DC
Screw terminal, 0.2 - 2.5 mm², 12-24 AWG, 0.5-0.6 Nm
23 V DC
23 V DC
0.8 V DC
1 V DC
0.5 A
2.0 A
1 V DC
1 V DC
12 W
12 W
12 VA (1.2 H)
100 Hz
100 Hz
Restart after removal of
overload
Thermal fuse
2701043
2701056
8
24 V AC/DC
80...250 V
0.17 mA AC
20 ms
100 m
2701043
2701056
AC/DC relay
4
30 V DC/250 V AC
5 A @ 30 V DC/5 A @ 120...250 V AC
5 A
20 A
600 W @ 24 
5 A @ 120 V AC / 5 A @ 240 V AC
1.5 @ 120 V AC / 0.9 @ 240 V AC
10 ms
4 ms
6
10 x 10
cycles
100,000 cycles
300 operations per minute
30 operations per minute
External protection required.
External protection required.
2701069
115/230 V
AC
0...25 V
2701069
2338_en_O