D 2.7 Temperature Expansion Module (Order No. 2701671); Temperature Inputs - Phoenix Contact Nanoline Series User Manual

Table of Contents

Advertisement

General
Dimensions (H x W x D)
Weight
Degree of protection
Connection method
Operating temperature range
Storage temperature range
Humidity (maximum) @25°C

Temperature inputs

Number
Connection method
Design
Connection
Input resistance
Accuracy @ 25°C ambient (3-wire connection)
Thermocouple
Sensor type
Connection
Accuracy
Sensor types and accuracy
Sensor type
PT100 DIN
PT100 SAMA
PT1000
B
E
J
K
N
R
S
T
2338_en_O
D 2.7
Temperature expansion module (Order No. 2701671)
Minimum temperature
-200°C
-100°C
-200°C
600°C
-100°C
-200°C
-100°C
-100°C
-50°C
-50°C
-100°C
103 x 40 x 43 mm
110 g
IP20
D-SUB 9
0...60°C
-25...85°C
90%
2
Screw terminal, 0.2 - 2.5 mm², 12-24 AWG, 0.5-0.6 Nm
Pt 100 DIN (alpha = 0.00385)
Pt 100 SAMA (alpha = 0.00392)
Pt 1000 (alpha = 0.00385)
2- or 3-wire
1 M
1% full scale
B, E, J, K, N, R, S, T
2-wire, shield
1.5% +1°C (CJC error)
Maximum temperature
850°C
457°C
850°C
1800°C
1000°C
1200°C
1373°C
1300°C
1769°C
1769°C
400°C
Accuracy
±1% full scale
±1% full scale
±1% full scale
±1.5% full scale +1°C (CJC error)
±1% full scale +1°C (CJC error)
±1% full scale +1°C (CJC error)
±1% full scale +1°C (CJC error)
±1% full scale +1°C (CJC error)
±1.5% full scale +1°C (CJC error)
±1.5% full scale +1°C (CJC error)
±1.5% full scale +1°C (CJC error)
PHOENIX CONTACT
115

Advertisement

Table of Contents
loading