Connecting Power, Inputs And Outputs - Phoenix Contact Nanoline Series User Manual

Table of Contents

Advertisement

Nanoline
24
PHOENIX CONTACT
1.
Clear any components around the desired mounting location on the enclosure.
2.
Using an appropriate tool for the enclosure material, cut a 119 x 93 ±0.5 mm hole in the
enclosure. Remove any burrs or sharp edges using a file or appropriate tool.
NOTE:
Do not make the hole in the enclosure too large or the Operator Panel will pass through.
Do not drill holes for the mounting screws; they do not pass through the enclosure wall.
3.
Place the four J-hooks in the slots on the sides of the Operator Panel. Alternating
between the J-hooks, turn the screws in the J-hooks clockwise until they tighten against
the enclosure. Torque each J-hook screw to 0.5 - 0.6 Nm.
Enclosure
panel
Slot
J-hook
Figure 2-17
Remote Operator Panel installation
2.4

Connecting power, inputs and outputs

The Nanoline system components use a screw connection technology for power and I/O
connection. Individual connection points are labeled on the housing surface with
appropriate identifiers. Use a small screwdriver to turn the screw counterclockwise to
release and clockwise to tighten wires after insertion into the appropriate position.
CAUTION:
Do not apply power to the Nanoline controller until directed to do so in the commissioning
(startup) procedure.
Operator