Panasonic FP Series Programming Manual page 924

Hide thumbs Also See for FP Series:
Table of Contents

Advertisement

TM_1s_FB
This timer for 1s units works as an ON-delay timer. If the start contact of the function block is in the
Description
ON state, the preset time SV (set value) is started. When this time has elapsed, the timer contact T
turns ON.
For the TM_1s_FB function block declare the following:
start
SV
T
EV
ON
Time
OFF
chart
start
X
SV
0
X
EV
0
ON
OFF
T
download
PROG mode
 The number of available timers is limited and depends on the settings in the system
registers 5 and 6.
 The system timer functions (TM_1s, TM_100ms, TM_10ms, and TM_1s) use the same
NUM* address area as the system timer function blocks (TM_1s_FB, TM_100ms_FB,
TM_10ms_FB, and TM_1s_FB). For the timer function blocks the compiler automatically
assigns a NUM* address to every timer instance. The addresses are assigned counting
downwards, starting at the highest possible address. In order to avoid errors (address
conflicts), these timer functions and function blocks should not be used together in a
project.
PLC types Availability of TM_1s_FB (see page 1332)
Timer for 1s intervals (0 to 32767s)
start contact
each time a rising edge is detected, the set value SV is copied to the elapsed
value EV and the timer is started
set value
the defined ON-delay time (0 to 32767s)
timer contact
is set when the time defined at SV has elapsed, this means when EV becomes
0
elapsed value
count value from which 1 is subtracted every 1s while the timer is running
RUN mode
Timer instructions
923