Ct_Fb Down Counter - Panasonic FP Series Programming Manual

Hide thumbs Also See for FP Series:
Table of Contents

Advertisement

Counter instructions
CT_FB
Counters realized with the CT_FB function block are down counters. The count area SV (set value)
Description
is 1 to 32767.
For the CT_FB function block declare the following:
Count
Reset
SV
C
EV
PLC types
Availability of CT_FB (see page 1319)
Data types
Variable
Data type
Count
BOOL
Reset
INT
SV
BOOL
C
INT
EV
Time chart
Count
OFF
Reset
OFF
SV
EV
ON
C
OFF
download
PROG mode
702
Down Counter
count contact
each time a rising edge is detected at Count, the value 1 is subtracted from the elapsed value EV
until the value 0 is reached
reset contact
each time a rising edge is detected at Reset, the value 0 is assigned to EV and the signal output C
is reset; each time a falling edge is detected at Reset, the value at SV is assigned to EV
set value
value of EV after a reset procedure
signal output
is set when EV becomes 0
elapsed value
current counter value
Function
count contact (down)
reset contact
set value
set when EV = 0
elapsed value
ON
ON
10
0
10
0
RUN mode