Input wiring
Voltage input
V0
Input instrument
I 0
V1
I 1
Input instrument
COM
V2
I 2
V3
I 3
V4
Input instrument
I 4
V5
Input instrument
I 5
COM
V6
I 6
V7
I 7
Connect input instrument between V and COM terminal.
A/D conversion values
Input current (mA)
A/D conversion value
0.0
0
2.5
500
5.0
1000
7.5
1500
10.0
2000
12.5
2500
15.0
3000
17.5
3500
20.0
4000
Processing if the range is exceeded
0mA or less (including
0
negative value)
20mA or more
4000
Input voltage (V)
A/D conversion value
0.0
0
0.5
400
1.0
800
1.5
1200
2.0
1600
Current input
V0
(ch0)
I 0
V1
I 1
(ch1)
COM
Input instrument
V2
(ch2)
I 2
V3
Input instrument
(ch3)
I 3
V4
(ch4)
I 4
V5
I 5
(ch5)
COM
Input instrument
V6
(ch6)
I 6
Input instrument
V7
(ch7)
I 7
First, connect both V terminal and I terminal. And then
connect input instrument between it and COM terminal.
Analog unit instructions
Input instrument
(ch0)
Input instrument
(ch1)
Input instrument
(ch2)
Input instrument
(ch3)
Input instrument
(ch4)
Input instrument
(ch5)
Input instrument
(ch6)
Input instrument
(ch7)
1099