Error
Name
code
No support error
!42
Multiple frames
!43
procedure error
Link setting error
!50
Transmission time-out
!51
error
Transmit disable error
!52
Busy error
!53
Parameter error
!60
Data error
!61
Registration over error
!62
PC mode error
!63
External memory error
!64
Protect error
!65
Address error
!66
No program error and
!67
no data error
Rewrite during RUN
!68
error
SIM over error
!70
Exclusive access
!71
control error
1314
Description
A non-supported command was received.
A different command was received when processing multiple frames.
A non-existing route number was specified. Verify the route number by
designating the transmission station.
Transmission to another device is not possible because the transmission buffer
is full.
Transmission processing to another device is not possible (link unit runaway,
etc.).
Processing of command received is not possible because of multiple frame
processing or because command being processed is congested.
Content of specified parameter does not exist or cannot be used.
There was a mistake in the contact, data area, data number designation, size
designation, range, or format designation.
Operation was done when number of registrations was exceeded or when there
was no registration.
PC command that cannot be processed was executed during RUN mode.
An abnormality occurred when loading RAM to ROM/IC memory card. There
may be a problem with the ROM or IC memory card. When loading, the
specified contents exceeded the capacity. Write error occurs.
 ROM or IC memory card is not installed.
 ROM or IC memory card does not conform to specifications
A program or system register write operation was executed when the protect
mode (password setting or DIP switch, etc.) or ROM operation mode was being
used.
There was an error in the code format of the address data. Also, when
exceeded or insufficient address data, there was a mistake in the range
designation.
Cannot be read because there is no program in the program area or the
memory contains an error. Or, reading of non-registered data was attempted.
When inputting with programming tool software, editing of an instruction (ED,
SUB, RET, INT, IRET, SSTP, and STPE) that cannot perform a rewrite during
RUN is being attempted. Nothing is written to the CPU.
Program area was exceeded during a program write process.
A command that cannot be processed was executed at the same time as a
command being processed.