Error
Name of error
code
Unit installation error
E27
System register error
E28
Interrupt error 0
E30
Interrupt error 1
E31
Interrupt error 2
E32
I/O status error
E34
I/O unit verify error
E42
Operation error
E45
Self-diagnosti
E100–E
c error set by
299
F148_ERR
40.10.3
MEWTOCOL-COM Error Codes
Error
Name
code
NACK error
!21
WACK error
!22
Unit no. overlap
!23
Transmission format
!24
error
Link unit hardware error
!25
Unit no. setting error
!26
No support error
!27
No response error
!28
Buffer closed error
!29
Time-out error
!30
Transmission
!32
impossible error
Communication stop
!33
No destination error
!36
Other communication
!38
error
BCC error
!40
Format error
!41
Operation
Description and steps to take
status of
PLC
Stops
The number of installed units exceeds the limit. Turn off the
power supply and check the restrictions on unit combinations.
Stops
Probably an error in the system registers. Check the system
register settings.
Stops
Probably a hardware problem. Please contact your dealer.
Stops
An interrupt occurred without an interrupt request. A hardware
problem or error due to noise is possible. Turn off the power
and check the noise conditions.
Stops
An interrupt occurred without an interrupt request. A hardware
problem or error due to noise is possible. Turn off the power
and check the noise conditions.
There is no interrupt program for an interrupt which occurred.
Check the number of the interrupt program and change it to
agree with the interrupt request.
Stops
A faulty unit is installed. Replace the unit with a new one.
Selectable
The connection condition of an I/O unit has changed compared
to that at the time of power-up. Check the error using
sys_wVerifyErrorUnit_0_15 and locate the faulty I/O unit. Set
the operation status using system register 23 to continue
operation.
Selectable
Operation became impossible when a high-level instruction was
executed. The causes of calculation errors vary depending on
the instruction. Set the operation status using system register
23 to continue operation.
E100–
Stops
The self-diagnostic error specified by the F148_ERR (see page
E199
1000) instruction occurred. Take steps to clear the error
condition according to the specification you chose.
E200–
Continues
E299
Description
Link system error
A transfer error occurred in the data received.
A formatting error in the command received was detected.
Appendix Programming Information
1313