F19_SJP
Jumps to the label LBL (see page 1013) s with the same number as the data stored in the area
Description
specified by s if the trigger EN is in the ON-state.
This instruction also exists as a P instruction (for FP2/2SH, FP3/5, FP10/10SH PLC types), which
is only executed at the rising edge of the EN trigger. Select [Insert P instruction] from the
"Instructions" pane if you require a P instruction. To facilitate reuse, the instruction then appears
under "Recently used" in the pop-up menu. Press <Ctrl>+<Shift>+<v> within the programming
area to open the list of recently used elements.
The range of the number s can be between 0 and 255.
Availability of F19_SJP (see page 1322)
PLC types
Data types
Variable
Data type
ANY16
s
Operands
For
WX
s
In this example, the same POU header is used for all programming languages. For an example
Example
using IL (instruction list), please refer to the online help.
POU header
The same POU header is used for all programming languages.
Body
When the variable start is set to TRUE, the function is carried out.
LD
Indirect jump to label
Function
Stores label number (0 to 255)
Relay
T/C
WY
WR
WL
SV
Program execution control instructions
Register
EV
DT
LD
FL
Constant
-