40.11 MEWTOCOL-COM Communication Commands
Command name
Read contact area
Write contact area
Read data area
Write data area
Read timer/counter set value area
Write timer/counter set value area
Read timer/counter elapsed value area RK
Write timer/counter elapsed value area WK
Register or Reset contacts monitored
Register or Reset data monitored
Monitoring start
Preset contact area (fill command)
Preset data area (fill command)
Read system register
Write system register
Read the status of PLC
Remote control
Abort
Code
Description
RC
Reads the on and off status of contacts.
(RCS)
- Specifies only one point.
(RCP)
- Specifies multiple contacts.
(RCC)
- Specifies a range in word units.
WC
Turns contacts on and off.
(WCS)
- Specifies only one point.
(WCP)
- Specifies multiple contacts.
(WCC)
- Specifies a range in word units.
RD
Reads the contents of a data area.
WD
Writes data to a data area.
RS
Reads the value set for a timer/counter.
WS
Writes a timer/counter setting value.
Reads the timer/counter elapsed value.
Writes the timer/counter elapsed value.
MC
Registers the contact to be monitored.
MD
Registers the data to be monitored.
MG
Monitors a registered contact or data using MD and MC.
SC
Embeds the area of a specified range in a 16-point on and
off pattern.
SD
Writes the same contents to the data area of a specified
range.
RR
Reads the contents of a system register.
WR
Specifies the contents of a system register.
RT
Reads the specifications of the PLC and error codes if an
error occurs.
RM
Switches the operation mode of the PLC.
AB
Aborts communication.