Climatic Operating Conditions; Mechanical Operating Conditions - ABB S800 Product Manual

Table of Contents

Advertisement

Climatic Operating Conditions

Climatic Operating Conditions
Temperature
Temperature
change
Humidity
Altitude
Pollution degree
Corrosive
atmosphere
(1) Approvals are issued for +5 to +55°C.

Mechanical Operating Conditions

Vibration Test
Sinusoidal
Operational
Shock
Emitted noise
116
Table 14. Climatic Operating Conditions
Condition
0 to +55°C non-condensing
0 to +40°C compact MTUs or S800L
(1)
modules on vertical DIN-rail, see 
Table
3 °C/min
RH = 5 to 95%, no condensation
2000 m
Degree 2
<1000 Angstrom copper corrosion over
28 days
<2000 Angstrom copper corrosion over
28 days
Table 15. Mechanical Operating Conditions
5–9 Hz, amplitude 3,5 mm
9-150 Hz, acceleration 1,0g
1 octave/min
150 m/s
<55 dB (A)
Section 3 Technical Data and Performance
Operative range
32, non-condensing
Operative range
2
, 11 ms
Standard
IEC/EN 61131-2
IEC 60664-1
ISA-71.04 
Severity level G2
ISA-71.04 
Severity level G3
Standard
IEC/EN 61131-2
IEC/EN 61131-2
3BSE015969-600 A