3.3.3

Operating SIMOTION D410 on PROFIBUS DP.

PROFIBUS DP interface (X21)
SIMOTION D410 provides an interface for connecting to PROFIBUS DP. The interface
supports transmission rates up to 12 Mbit/s.
The X21 interface can be operated as a:
● DP slave, isochronous
● DP master, isochronous
● DP slave, not isochronous
● DP master, not isochronous
● MPI interface
Both PROFIBUS DP interfaces are set by default for operation as master at address 2 at a
transmission rate of 1.5 Mbit/s. The PROFIBUS DP network is automatically detected and
generated for this setting.
However, you can select other settings. Such user-specific settings must be configured in
HW Config and NetPro.
Note
Communication with the SINAMICS Integrated of a D410 is always equidistant. Here, the
SIMOTION D410 is the master and the SINAMICS Integrated drive is the slave.
3.3.4

Creating a new PROFIBUS DP subnet

The SIMOTION D410 device is networked using SIMOTION SCOUT. Set up your user-
specific bus parameters for the PROFIBUS interface when you configure the network.
Note
The actions outlined below only need to be taken if you have not selected an interface when
integrating the SIMOTION D410 into the project (refer to section Creating a project and
configuring the communication (Page 45)).
Next the connection to the PG/PC must be established via NetPro, refer to:
• Section Configuring the PROFIBUS PG/PC interface (only for D410 DP) (Page 49)
• Section Configuring the Ethernet PG/PC interface (only for D410 PN) (Page 50).
1. Double-click the "D410" entry in the Project Navigator in order to open HW Config.
2. Double-click the DP/MPI interface in the SIMOTION D410 representation in HW Config.
3. Click "Properties" in the "General" tab to open the "PROFIBUS interface DP/MPI" dialog
SIMOTION D410
Commissioning Manual, 02/2012
The "Properties - DP/MPI" dialog box opens.
box.
3.3 Configuring the PROFIBUS DP interface (only D410 DP)
Parameter assignment / addressing
55