5.2

Replacing modules (spare part scenario)

5.2.1

Spare parts replacement for SIMOTION D410

Use of used modules
If a used D410 is used for the module replacement, we recommend that the retained data be
deleted from the used D410.
Two options are available for this.
Table 5- 1
Option
Module memory reset
Deleting and restoring non-
volatile SIMOTION data
NOTICE
When the operating mode switch is set to switch position (MR), switching the power
OFF/ON performs "Restore factory settings" instead of "Memory reset".
"Restore factory settings" deletes all the project data from the CompactFlash Card.
To avoid and unintentional/accidental deletion of the project data on the CompactFlash
Card, we recommend that the retain data be deleted via the Service selector switch.
SIMOTION D410
Commissioning Manual, 02/2012
Options for deleting the retain data
Reference to description
Refer to section Resetting the
memory of SIMOTION D410
(Page 150)
Refer to section Deleting/restoring
non-volatile SIMOTION data
(Page 207)
Maintenance and service
5.2 Replacing modules (spare part scenario)
Notes
Control via an operating mode
switch (setting MR).
This is available on all
SIMOTION platforms
Control via a service switch.
This is available only on
SIMOTION D.
165