Fault Handling
5.2

Potential Faults in Motor Starters with PROFIBUS-DP

Motor starter: 3RK1303-2AS54-1AA.
Potential faults
Bus fault
Process image
error
Undervoltage
AS-i
Undervoltage
AUX PWR
No main power
supply
Sensor supply
overload
Temperature
sensor
overload
Temperature
sensor
short-circuit
Temperature
sensor
wire break
Self-test fault
(device fault)
Switching ele-
ment defective
*
Once the cause of the fault has been removed, the fault is acknowledged automatically regardless
of the parameters set (not to be confused with autoreset).

Table 5-1: Faults and fault handling for 3RK1 303-5BS44-1AA.

5-4
Action
LED
indicator
Switch substi-
AS-i: red
tute value
Trip
SF: red
Trip
SF: red
Trip
SF: red
Fault not recognized!
Trip
SF: red
Warning/
SF: red
Trip
SF: red
Warning/
SF: red
Trip
SF: red
Warning/
SF: red
Trip
SF: red
Trip
SF: red
Trip
SF: red
STATE: red
Acknow-
Comment
ledged by
*)
Auto
Check the communication con-
nection to the field bus master.
Possible causes of faults:
• Bus line severed
• Field bus master defective
OFF
Deactivate the Motor CW/CCW
command
control command.
*)
Auto
Check the power supply.
U
< 18 V
DC24V-NS
*)
Auto
Check the power supply.
U
< 18 V
DC24V-S
If the motor cannot be switched
on even though it is properly
connected and power has been
applied, the internal fuses are
defective. − > Replace the device!
Trip reset
Check the sensor supply.
I
> 200 mA
Sensor
*)
Auto
Wait until the motor has cooled
down.
Autoreset/
Wait until the motor has cooled
trip reset
down.
Acknowledge after motor has
cooled down.
If acknowledgement is not pos-
sible, the motor is still too hot.
*)
Auto
Remove the short-circuit on the
temperature sensor lead.
Autoreset/
Remove the short-circuit on the
trip reset
temperature sensor lead.
Acknowledge once the fault has
been rectified.
*)
Auto
Remove the wire break on the
temperature sensor lead.
Autoreset/
Remove the wire break on the
trip reset
temperature sensor lead.
Acknowledge once the fault has
been rectified.
Power OFF
Switch the device off and then
back on.
Power OFF
If a device fault is reported
again, the device must be
replaced.
ECOFAST Motor Starters
GWA 4NEB 950 5221-12 DS 02