Commissioning (software)
4.14 Optimizing the drive and controller
4. Select "Speed controller setpoint jump" as the measuring function. You can change the
5. Download the changes to the drive by clicking
Starting the measuring function
1. Click "Assume control priority" to assume control priority.
2. Click the "Drive ON" button to enable the drive.
144
values in the following fields: "Settling time", "Amplitude", "Offset", "Ramp-up time", and
"Measuring time".
Four channels can be recorded. Depending on the measuring function, certain channels
are preassigned.
Figure 4-37
Speed controller measuring function
Read the notice that appears and click "Accept" to confirm.
(Download Parameter Assignment).
Commissioning Manual, 02/2012
SIMOTION D410