Maintenance and service
5.2 Replacing modules (spare part scenario)
Procedure for installing a component
1. Mount the component and reconnect the supply voltage.
2. Reconnect the DRIVE-CLiQ cable at the same location (port). The cable must be the
3. Activate the affected component or drive object.
Parameters for topology comparator and component replacement
In the expert list, you can use CU parameter p9906 to specify how the electronic rating
plates are compared for all the components of a Control Unit. The type of comparison can be
changed for each individual component at a later point in time, using p9907/p9908 or by
right-clicking in the topology. All data on the electronic rating plate are compared as
standard.
● When p9909 = 1, the serial number and the hardware version of the new replacement
● When p9909 = 0, serial numbers and hardware versions are not automatically
The setting p9901 = 1 enables the spare parts/components replacement without tool support
to be carried out. The new serial number of the spare part is automatically transferred from
the actual topology to the reference topology and saved in the non-volatile memory. In order
for this to occur, the components that have been replaced must be of the same type and
have the same order number, such as "6SL3055-0AA0-5BA0". The last or last two digits of
the order number (depending on the component type) are not checked, as the HW version,
for example, is coded in these. This mechanism is also applied when several components
are replaced.
Modified wiring following module replacement
In the default setting for the topology comparator, modified wiring configurations of the
DRIVE-CLiQ components (e.g. a cross-exchange) are not accepted for safety reasons and
are generated by a fault.
If a cross-exchange of components is required (i.e. existing components are replaced with
other existing components, and no spare parts are used), e.g. for troubleshooting purposes,
the topology comparator must be reduced via parameter p9906 or preferably via
p9907/p9908; or as an alternative, by right-clicking in the topology.
NOTICE
In this case, incorrect insertion of components is no longer monitored.
168
same length as the old one.
WARNING
In order to replace this component, the module must be in a de-energized state.
component are automatically transferred from the actual topology to the reference
topology, and then saved in the non-volatile memory.
transferred.
SIMOTION D410
Commissioning Manual, 02/2012