Siemens SIMOTION D410 Series Commissioning Manual page 181

Hide thumbs Also See for SIMOTION D410 Series:
Table of Contents

Advertisement

Selecting the TP product version
The desired technology package is selected with fine granularity in SIMOTION SCOUT at
"Target device" > "Select technology packages ...".
Figure 5-9
Note
Device diagnostics can provide information on which technology package product version
has been loaded to a CPU.
Loading technology packages to the target device
Technology packages are only loaded to the target device if no technology package has
been loaded so far or if "Load to file system" is executed.
If a technology package version changes, the technology package must be explicitly
reloaded to the target device. To do this, proceed as follows:
1. Select "Download project to target system" in SIMOTION SCOUT.
2. Under "Additional CPU options", select the "Replace product versions of the technology
For further information, please refer to the online help for SIMOTION SCOUT.
SIMOTION D410
Commissioning Manual, 02/2012
5.3 Adapting a project (Upgrading the project / Replacing the SIMOTION controller)
Select Technology Packages
packages" option and confirm with "OK".
Maintenance and service
181