Siemens SIMOTION D410 Series Commissioning Manual page 204

Hide thumbs Also See for SIMOTION D410 Series:
Table of Contents

Advertisement

Diagnostics data
6.2 Diagnostic data and non-volatile SIMOTION data
Service selector switch
Data are backed up using a service selector switch as follows:
1. Set the service selector switch to "Diagnostics" (i.e. set DIP switch S7 to ON).
2. Switch the SIMOTION D410 off and on again.
3. Wait for the device to start up.
4. Once the backup is complete, switch off the D410.
5. Remove the CompactFlash Card and reset the service selector switch to its original
INI file in the main CompactFlash Card directory
1. Use a text editor (such as Notepad) to create a file called simotion.ini.
2. Add the following text: DIAG_FILES=1
3. Copy the simotion.ini file to the main CompactFlash Card directory.
4. Insert the CompactFlash Card into the module, which is switched off.
5. Switch the SIMOTION D410 on and allow the SIMOTION device to start up.
6. Once the backup is complete, switch off the SIMOTION device.
7. Remove the CompactFlash Card.
204
The switch positions of the mode selector switches are not relevant (i.e. the operating
mode set remains unchanged).
Figure 6-3 Writing diagnostic data using a switch position
The diagnostic data and non-volatile SIMOTION data is backed up to the CompactFlash
Card during power-up, provided that this is still possible and is not prevented by HW
defects, for example. The status LEDs indicate the backup process on the
SIMOTION D410 as follows:
– Backup in progress: RUN/STOP LED flickers yellow
– Backup complete: RUN/STOP LED flickers green
setting.
You must use a text editor and may not use any formatting in the text.
The diagnostic data and non-volatile SIMOTION data are backed up to the data carrier
during startup, provided that this is still possible and is not prevented by HW defects,
for example. The status LEDs indicate the backup process on the SIMOTION D410 as
follows:
– Backup in progress: RUN/STOP LED flickers yellow
– Backup complete: RUN/STOP LED flickers green
SIMOTION D410
Commissioning Manual, 02/2012

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotion d410 pnSimotion d410 dp

Table of Contents