Parameter assignment / addressing
3.3 Configuring the PROFIBUS DP interface (only D410 DP)
3.3.2

Assignment of the PROFIBUS addresses in HW Config

Assigning PROFIBUS addresses
Assign a PROFIBUS address to all devices before you start networking these in order to
enable intercommunication.
Note
All PROFIBUS addresses you assign must be unique on the PROFIBUS subnet.
Information pertaining to the rules of communication on the PROFIBUS subnet is available in
the
Define the PROFIBUS address separately for each device on your programming device / PC
in HW Config. Certain PROFIBUS DP slaves are equipped with an address switch.
Note
The PROFIBUS addresses set at the devices using these switches must correspond with the
address settings in HW Config.
Recommendation for PROFIBUS addresses
Reserve PROFIBUS address "0" for a service programming device and "1" for a service HMI
device which are connected to the subnet as required.
Recommended PROFIBUS address setting for SIMOTION D410 in case of replacement or
service:
Reserve address "2" for a SIMOTION D410. This prevents redundancy of the addresses
after SIMOTION D410 is installed in the subnet with default settings (for example, when
replacing a SIMOTION D410). Assign addresses higher than "2" to any additional devices on
the subnet.
54
SIMOTION D410
Manual.
SIMOTION D410
Commissioning Manual, 02/2012